Specifications for Argus’ Cordex Controller Panel/Rack Mount Continued
Argus Technologies Ltd. 018-587-B1 Rev A WC
Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved. Page 2 of 3
Hardware Specifications
CPU: Coldfire
RAM: 8MB
Flash: 4MB standard, 4MB optional
Display: 160 x 160 pixel grayscale LCD
Front Panel Controls: Reset button and touch panel (display and input device)
LED’s: System OK (Green)
Power System Minor Alarm (Yellow)
Power System Major Alarm / Controller Fail (Red)
Internal Battery: 3V Lithium CR1616 [Argus part number #185-005-10]
Audio: Built-in speaker for alarm and popup message tones
Mounting: Integrated with power system/distribution panel [List 80]
19" and 23" flush rack mounting, 3RU [Default List 81]
Rack Mount Dimensions: 131mm H x 431mm W x 100mm D
(5.1” x H x 16.9” W x 3.9” D)
Weight: 6.2 kg typical [Default List 81]
(13.8 lb.)
Analog Inputs: 2 DC voltage, 1 DC current, 2 temperature, 1 bi-voltage
[sample configuration – other options available]
Digital Inputs: 8 for CXCP/CXCR; 4 for CXCM
Relay Outputs: 8 Form C, 60Vdc 1A maximum; 8 optional
Communication Ports: Ethernet port, CAN (bus), RS-485, 2 x RS-232
Recommended Connection Wire Sizes (as per UL/CSA)
Wire Size Range: #20 to #30 AWG
(0.5 to 0.05mm
2
)
Temperature Range: 0 to 50°C
(32 to 122°F)
CAUTION – TO REDUCE RISK OF FIRE, USE ONLY #26 AWG (0.14mm
2
) OR LARGER WIRE.