018-340-B0-001 Rev. A
2.0 Installation, Con guration and System Interface, continued
2.2 ACM-96 and ACM-96G, continued
2.2.2 APS-CP Generator Controller Con guration
Locate the Dip Switch on the APS-CP by removing the screws in the bottom corners
and lifting the front cover. If it is a 5-position Dip Switch, set switches 1 and 5 to the
ON position.
If it is a 4-position Dip Switch, leave default switch positions.
2.2.3 ECI-2 Con guration
The ECI-2 Engine controller can be directly connected. No changes are required for
con guration.
Fig. 2-5, 5-Position APS-CP Dip Switch
Fig. 2-6, ECI-2 Engine Controller
ACM-96G requires Genasys DC Bus Harness
NOTE:
ACM-48 and ACM-36 models are also available and can be installed to directly replace existing CE style
stand-alone AlphaGen ACU units.