LA-P Receptacle
2.5 Rack-mount Installations
The APC is also available in a rack-mount version that can be installed into a
standard 19” rack. The APL is not available in a rack-mount model.
NOTE: BEFORE INSTALLING THE APC, ENSURE THAT ALL OPTIONS HAVE
BEEN INSTALLED AND PROPERLY CONNECTED. REFER TO SECTION 2.11
OPTIONS, FOR INSTALLATION INSTRUCTIONS.
Procedure: Photo 2.5.a
1. To mount the APC into a standard 19” rack, use 10-32 screws and cup
washers (not supplied by Alpha) to secure the APC to the rack rails. Leave
1” clearance above and below the 7” panel height for clearance and cooling
when other equipment is installed in the rack. If other APC power supplies
are installed in the same rack, they may be stacked without clearance
between them, but leave sufficient clearance between the top and bottom
supplies in the stack, and adjacent equipment or walls. If an enclosed rack
or cabinet is used, leave at least 2” clearance between the transformer and
surrounding wall panels, and provide ventilation through the use of louvered
rear panels (or leave open if permissible).
2. The APC is supplied with an additional 3’ (1.0m) power cord. This cord
connects between the short cord on the rack-mount APC and a standard
receptacle box.
3. The APC is now ready for the operation (see section 3.1 START-UP AND
TEST).
Rack mounting slots
Ammeter
Fuse
Push-push circuit breaker
TDR-M adjustment
access hole
Photo 2.5.a
APC Rack-mount (120 VAC Version)
2. INSTALLATION
15
SIL-C