2.7 Connecting Utility Power
CAUTION: THE FOLLOWING SHOULD BE PERFORMED ONLY BY QUALIFIED
SERVICE PERSONNEL AND IN COMPLIANCE WITH LOCAL ELECTRICAL
CODES. CONNECTION TO UTILITY POWER MUST BE APPROVED BY THE
LOCAL UTILITY BEFORE INSTALLING THE POWER SUPPLY.
NOTE: UL AND NEC REQUIRE THAT A SERVICE DISCONNECT SWITCH (UL
LISTED) BE PROVIDED BY THE INSTALLER AND BE CONNECTED BE-
TWEEN THE POWER SOURCE AND THE ALPHA POWER SUPPLY.
2.7.1 Wiring the Enclosure’s Utility Service: Photos 2.7.1.a, .b
The following does not apply to the rack-mount model (RM) or the shelf-mount
model (SM) which plug into a receptacle in the rack or enclosure. The APL model is
connected to the utility power via the APL’s terminal block (Photo 2.7.1.b).
Utility power enters the enclosure through a 0.875” diameter opening at the bottom
of the APC enclosure (Photo 2.7.1.c). The enclosure accepts a standard conduit
fitting. When used in conjunction with the PED-M metered, ground-mount
enclosure, utility power enters through a dedicated raceway.
2. INSTALLATION
19
NOTE: BEFORE PROCEEDING, VERIFY THAT THE UTILITY POWER IS NOT
ENERGIZED! DO NOT PLUG THE APC INTO THE AC RECEPTACLE AT THIS
TIME.
2.7.1.1 Procedure: (120VAC, 60 HZ) Photo 2.7.1.1
If the Modular Transformer Assembly (MTA) is installed it must be completely
removed during utility wiring. To remove the transformer assembly, loosen the
captive screw on the bottom of the baseplate and remove the transformer assembly.
1. Loosen the two captive screws securing the receptacle box. Turn the
receptacle box over to expose the internal wiring.
2. Route the utility conduit through the 0.875” diameter opening located at the
bottom of the APC. Secure the fitting with a locknut.
3. Connect the utility BLACK-HOT wire (120 VAC; 60 Hz) to the BLACK wire
inside the receptacle box using the existing wire nut.
4. Connect the WHITE-NEUTRAL wire to the WHITE wire inside the
receptacle box using the existing wire nut.
Ground lug for
grounding rod
Utility input
SIL-C option
60 VAC output
VSF connector
Photo 2.7.1.a
APC Bottom View
Photo 2.7.1.b
APL Wiring
NEUTRAL
wire
GROUND
wire
HOT
wire