Status Monitoring
AlphaNet
DSM3
DOCSIS
®
Status Monitor
AlphaNet DSM
Specifications
Power Supply Models
Supported:
XM2-HP, XM2-300HP, XM2, GMX
Battery Monitoring: Up to four strings of 36V or 48V batteries
Power System Management:
Up to five power supplies and an AlphaGen
generator are managed from a single DSM3.
Coordinated battery charging, system test and
aggregated alarm reporting are each managed
by the DSM3
Management Protocol:
Standard ANSI/SCTE HMS MIBs support basic
power supply monitoring. Advanced diagnostics
with battery and power module analytics available
via secure SNMP
Advanced Diagnostics
1
Intelligent Power Supply
Interface:
Power supply user interface displays advanced
diagnostics including: DOCSIS modem upstream
and downstream RF levels, IP address assigned by
network DHCP server, MAC address andrmware
levels, individual battery voltages to verify correct
wire harness installation.
Battery State of Health:
Power supply internal analytic diagnostics report
when batteries should be serviced. Reported
Status:
Batteries OK,
Battery Thermal Warning – PM Visit
Recommended,
Battery Conductance Warning - PM Visit
Recommended,
Battery Thermal Alarm – Service Required
Battery Conductance Alarm - Service Required
Power Inverter State
of Health:
Power supply internal diagnostics report if the
power inverter requires service.
Reported Values: Inverter OK, Replace Inverter.
Battery Conductance:
Individual battery conductance measurements
(Mho’s) from portable meters are using the power
supply or DSM craft interface.
Battery Thermal Variance:
Temperature delta between enclosure ambient
and battery (-) terminal is automatically logged.
Hardware
RF Cable Interface:
F-connector, female, 75 Ohm, connector angle
accommodates coax bend radius when installed
in some enclosures
Local Interface: RJ-45, Ethernet, multi-mode operation
LED Indicators:
Ready/Alarm, Upstream Registration,
Downstream Lock, AlphaBus, RF Level, Link,
CPE Traffic, Battery Harness Correct
I/O Control: 4-pin Molex: Digital Input, Digital Output, 5V, Common
AlphaBus:
RJ-11 offset tab: Multi-power supply and
AlphaGen communications
Battery Monitoring:
8-pin Molex battery string A/B, 8-pin Molex
battery string C/D
Tamper:
NO or NC, software configurable, reads
enclosure door magnetic switch
1
Advanced diagnostics are available through Alpha Certified network monitoring systems
Environment
Operating Temperature: -40 to 65°C / -40 to 149°F
Storage Temperature: -40 to 85°C / -40 to 185°F
Humidity: 10 to 90% non-condensing
Regulatory Compliance:
FCC Part 15 Class A
EN 50083-2:2006 EMC Requirements for CATV Equipment
EN 62040-2:2006 Uninterruptable Power Supply EMC
Requirements, Category C2
Surge: IEEE 587, Category B3
RoHS: Directive 2002/95/EC
Network Communications
DOCSIS (RF) Port Protocols: IP, UDP, TCP, DHCP, TFTP, SNMPv1, SNMPv2c, HTTP
Ethernet Port:
Local Mode: HTTP web interface for local
craft diagnosis.
CPE Mode: DOCSIS Cable modem Ethernet
CPE functionality
MIBs:
Power Supply (ANSI/SCTE 38-4)
Other SCTE HMS MIBs as defines by the SCTE
for power supply and generator status monitoring
Alpha proprietary advanced UPS diagnostics
Power Supply Monitored Parameters
Major Alarm:
Aggregate alarm consisting of: test fail, battery
fail, line isolation alarm, output overload, inverter,
over-temperature, N+1 active, fuse fail
Minor Alarm:
Aggregate alarm consisting of:
temperature probe error, AC line loss, N+1 error
Input Voltage: Reported from power supply V(in) measurement
Output Voltage: Reported from power supply V(out) measurement
Output Current 1-4:
0-25A standard on port 1. Ports 2-4 require
power supply option.
Output Power: Calculated, reported in AC Watts
UPS Status: AC Line, Standby, Test in process, Test alarm
Enclosure Door: Open or Closed
Battery Voltage:
Individual battery voltage, up to four strings of 3
or 4 batteries (maximum 16 batteries), +/- 100mV
per battery
Battery Temperature:
Reported from power supply battery Remote
Temperature Sensor (RTS)
Remote Test Control: Start / Stop power supply test cycle
Generator Monitored Parameters
Status: Generator Off, Running, Alarm
Generator Alarm:
Aggregate alarm consisting of: low oil pressure, engine
over-temp, engine over-speed, crank limit, over voltage,
low fuel, water intrusion, pad shear, gas hazard, test fail
Gas Hazard: OK, Alarm
Water Intrusion: OK, Alarm
Pad Shear: OK, Alarm
Enclosure Door: Closed, Open
Ignition Battery Voltage: +/- 100mV
Enclosure Temperature: +/- 2°C
Low Fuel: OK, Alarm
Remote Test Control: Start / Stop generator test cycle
Cable Modem:
Compliance: DOCSIS 1.1 and 2.0
Transmit Frequency Range: 5 to 42 Mhz
Receive Center Frequency Range: 91 to 857 Mhz
Output Power Range: 8 to 58 dBmV
Input Signal Range: -15 dBmV to 15 dBmV
Channel Bandwidth: 6 Mhz
> Embedded network management for Alpha broadband power supplies
> Standard network interface including SNMP, Web access and ANSI/SCTE HMS MIBs
> Battery and power supply advanced diagnostics reduces truck
rolls and overall operating expense of powering network
> Optional VoIP testing features
AlphaNet DSM3
Zobrazit stránku 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 55 56

Komentáře k této Příručce

Žádné komentáře