Battery Accessories
AlphaGuard
Models:
AG-CMT-3:
AlphaGuard Charge Management SC, 36V
—including 36Vdc battery string interface cable
AG-CMT-4:
AlphaGuard Charge Management SC, 48V
—including 48Vdc battery string interface cable
Configuration
Quantity: One (1) AlphaGuard is required per battery string
Service Location: With the battery string
Mechanical
Housing Material: High impact plastic
Dimensions
H x W x D (in/mm):
1.4 x 4.8 x 4.3 / 36 x 122 x 108
Weight (lb/kg): 0.8 / .36
Electrical
Batteries:
Individual 12Vdc nominal batteries configured
into 36 or 48Vdc strings
Circuit Protection: Fast blow fuse, reverse polarity protected
Quiescent Current Draw:
1mA max. (Current consumed by AlphaGuard
after low voltage total shutdown)
Charge Management: Most effective during float period of charge
Max. Current: 2A @ 25°C / 77°F
Quality of Final Balance: ±100mV max. between any two (2) batteries
Charging Efficiency: 80 to 90%
Charge Balance: ±100mV typical
Low Voltage Cutoff: 34.5Vdc/46Vdc ±5%
Communication to XM2:
AG-DSM cable supplies battery readings to a
DSM status monitoring card
Voltage Sense Regulation: ±100mV
Environment
Operating Temperature: -40 to 55°C / -40 to 131°F
Humidity 5 to 95% non-condensing
Warranty
Warranty: 5 years
The AlphaGuard employs a patented Charge Management
Technology (CMT) to shuttle excess charge current to batteries
requiring a greater charge, and is contained in a small plastic
enclosure that installs directly on top of one the batteries in the
string or in the optional battery integration tray. A short service
cable connects the AlphaGuard to each of the batteries in the
string. Both 36Vdc (3 battery) and 48Vdc (4 battery) versions are
available. One AlphaGuard is required per string.
An AlphaGuard configured with the optional voltage sense
cabling and interface module (DSM, ESM, EDSM or External
DOCSIS
®
) allows the AlphaGuard to interface with a status-
monitoring module. Two AlphaGuard modules can be
connected to single interface module. Refer to individual
interface module documentation for additional information.
> Extends battery life
> Spreads charge voltage equally across batteries
> Compensates for battery differences as they age
> Replace single batteries, not the entire string
> Single battery connections for charge
management and status monitoring
> Safe unattended operation designed to CSA
C22.2 No. 107.1 and UL 1778 Standards
> Optional Potted AlphaGuard for
underground battery vault applications
AlphaGuard
Battery Charge Management System
Potted AlphaGuard CMT-3
AG-DSM-S9-Cable AG-DSM-D9-Cable AG-DSM-D35-Cable AG-DSM-S35-Cable Battery Cable 36V 6ft Battery Cable 48V 6ft
AlphaGuard CMT-3
Zobrazit stránku 49
1 2 ... 45 46 47 48 49 50 51 52 53 54 55 56

Komentáře k této Příručce

Žádné komentáře